Instrument Transformers · CT Secondary Burden
CT Burden Calculation: Why the Secondary Leads, Not the Relay, Decide the Verdict
A 2.50 VA relay on a 400/5 CT looks like a light load — until you add 20 m of 2.5 mm² copper and the leads alone draw 6.90 VA. How the lead-burden square law works, where the verdict flips, and why the same circuit on a 1 A secondary carries exactly 25 times less.
Published 2026-08-02 · EI Portal
The most common CT burden calculation mistake is adding up only the relay. A current transformer drives the whole secondary loop — the connected device plus the wiring back to the panel — and on a 5 A secondary the wiring is usually the bigger load. Count only the device VA and you can sign off a CT that is quietly running over its rated burden. A CT secondary burden check exists to make the leads explicit, and to tell you how much cable run you have left before the core is full.
What rated burden means
A CT's rated burden is the VA it is designed to drive at rated secondary current. The burden check is a budget: does everything hanging on the secondary fit inside that VA? The verdict is a three-state comparison of utilisation against the rating — >100% is "Over burden", ≥85% is "Near limit", anything else is "Within rating".
The lead-burden method
Every number below comes from one short chain, referred to the secondary:
lead loop = 2 × one-way length
lead resistance = ρ × loop / area (ρ Cu 0.017241 Ω·mm²/m at 20 °C)
lead burden VA = Isec² × lead resistance
total burden = connected + lead
utilisation % = total / rated × 100
max one-way length = (available VA ÷ Isec²) × area ÷ (2ρ)
The term that carries the surprise is Isec² × lead resistance. Lead burden scales with the square of the secondary current — which is why the same length of copper is a non-event on a 1 A circuit and the dominant load on a 5 A one.
Worked: the 400/5 feeder circuit
The tool's default case is a feeder protection circuit: a 400/5 CT with a 15.00 VA rated burden, a numerical relay drawing 2.50 VA, and 20 m one-way of 2.5 mm² copper to the panel. The chain runs:
- Two-wire loop: 2 × 20 m = 40.0 m
- Lead resistance: 0.017241 × 40.0 ÷ 2.5 = 0.276 Ω
- Lead burden: Isec² × R = 25 × 0.276 = 6.90 VA — the relay is only 2.50 VA
- Total burden: 2.50 + 6.90 = 9.40 VA = 62.6% of the 15.00 VA rating
Verdict: "Within rating", with 5.60 VA of margin, an equivalent burden of 0.376 Ω, a secondary loop voltage of 1.88 V, and a maximum one-way lead length of 36.3 m. Do the last division yourself: 6.90 ÷ 9.40 puts the leads at 73.4% of the total burden. The copper, not the relay, is the load on this core — count only the device and you would have logged about a quarter of the truth.
Where the verdict flips
Hold everything else and stretch only the lead run, and the three states walk past in order:
- 20 m → 62.6% → "Within rating"
- 30 m → 85.6% → "Near limit" — over the ≥85% line, so a marginal circuit never reads as a confident one
- 40 m → "Over burden" — total 16.29 VA against the 15.00 VA rating, margin −1.29 VA
The hero circuit's own readout told you where the edge was: the maximum one-way length was 36.3 m, and 40 m is past it.
The 1 A rescue — the 25× law
Keep the identical circuit — same 20 m, same 2.5 mm² copper, same relay — and swap the secondary to 1 A. The lead resistance does not change; the current in it does:
- Lead burden: 0.28 VA — versus 6.90 VA at 5 A, exactly 25× less
- Total: 2.78 VA = 18.5% utilisation
- Maximum one-way lead length: 906.3 m
That 25 is not a coincidence: (5/1)² = 25, straight from the Isec² law. Same cable, same device — a twenty-fifth of the lead burden, and twenty-five times the reach. This is why large substations and long secondary runs specify 1 A CTs.
When the leads alone bust the rating
The square law cuts the other way on the tool's long-run preset: an 800/5 CT, 15 VA rated, a 3.00 VA relay, and 45 m of 2.5 mm² copper. The leads alone draw 15.52 VA — more than the entire rating before the relay is even connected. Total 18.52 VA = 123.4% → "Over burden", margin −3.52 VA. The maximum run on that core was 34.8 m; 45 m busts it. Nothing about the relay caused this — the cable did. The full walk-through — the feeder circuit both ways and this failure — is in the worked case, the copper was the load.
Different circuits, same method
- Metering core — 200/5, 10 VA rated, a heavy 5.00 VA meter, and only 12 m of leads: lead burden 4.14 VA, total 9.14 VA = 91.4% → "Near limit", maximum run 14.5 m. A short run, but a big connected device on a 5 A secondary sits close to the edge.
- Numerical relay on 1 A — 400/1, 5 VA rated, a 0.5 VA relay, and 35 m of thin 1.5 mm² copper: lead burden 0.80 VA, total 1.30 VA = 26.1% → "Within rating", maximum run 195.8 m. Even thin cable stays comfortable at 1 A.
Big device or long leads, 5 A or 1 A — the budget is the same; only the term that dominates it changes.
Check it live
The CT Burden Quick Checker puts the whole chain on one surface: the lead resistance, the lead burden, the total against the rated VA, the utilisation, the equivalent burden and loop voltage, the maximum one-way lead length you have left — and the verdict, "Within rating", "Near limit" or "Over burden". Change the lead length, the conductor size or the secondary current and watch the decision move.
It is a rated-burden quick check, and it says so. It does not assess CT accuracy class, ALF, knee-point voltage, excitation current, remanence, saturation, transient offset or relay operating thresholds — that depth is the EI Portal CT Selection tool. Lead burden is estimated from a two-wire loop at 20 °C; resistance rises with temperature, so use project cable data where you have it, and confirm the core against the manufacturer's / IEC 61869-2 ratings. It is not a CT certification, and there is no PDF or report export.
Frequently asked questions
How do I calculate CT secondary burden?
Total everything the CT drives: the connected device's VA plus the lead burden. Lead burden = Isec² × lead resistance, where the resistance is taken over the two-wire loop (2 × one-way length) at ρ Cu 0.017241 Ω·mm²/m at 20 °C. Compare the total against the rated VA: a 400/5 CT with a 2.50 VA relay and 20 m of 2.5 mm² copper totals 9.40 VA on a 15.00 VA core — 62.6% utilisation, "Within rating".
Why do the leads dominate CT burden on a 5 A secondary?
Because lead burden scales with the secondary current squared. At 5 A, every ohm of loop resistance costs 25 VA — so 0.276 Ω of copper draws 6.90 VA while the relay it feeds draws only 2.50 VA. Work the division and the leads are 73.4% of the total burden on the worked feeder circuit. On a 5 A secondary the wiring, not the device, usually fills the core.
What is the difference between 1 A and 5 A CT burden?
For identical leads, the 5 A circuit carries exactly (5/1)² = 25 times the lead burden of the 1 A circuit. The worked 20 m run draws 6.90 VA at 5 A and 0.28 VA at 1 A, and the maximum one-way lead length jumps from 36.3 m to 906.3 m. That single square law is why long runs and large substations specify 1 A secondaries.
How long can CT secondary leads be?
Rearrange the burden budget for length: max one-way length = (available VA ÷ Isec²) × area ÷ (2ρ), where available VA is the rated burden minus the connected device. The worked 400/5 circuit has 36.3 m of reach on 2.5 mm² copper; the same circuit at 1 A has 906.3 m. On the 800/5 long-run preset the limit was 34.8 m — which is why its 45 m run reads "Over burden".
Is a rated-burden check enough to select a CT?
No — it is the VA budget only. It does not assess accuracy class, ALF, knee-point voltage, excitation current, remanence, saturation, transient offset or relay operating thresholds; that depth is the CT Selection tool. Use the quick check to catch an over-burdened secondary early — especially a long lead run — then confirm the core against manufacturer / IEC 61869-2 ratings and the protection study.